CORC  > 兰州理工大学  > 兰州理工大学  > 电气工程与信息工程学院
Research on the Fault Location Method of Double-terminal MMC-HVDC Transmission Line without the Influence of Wave Velocity
Zhang, Mingguang1,2,3; Yang, Chengming1,2,3; Liu, Zilin1,2,3; Chang, Jianhua1,2,3
2020-11-06
会议日期June 21, 2020 - June 22, 2020
会议地点Beijing, China
关键词Acoustic wave velocity Electric lines Location MATLAB Wave propagation Wavelet transformsGrid connections HVDC transmission lines HVDC transmission system Positioning accuracy Traveling wave fault locations Traveling wave locations Traveling-wave velocity Voltage traveling waves
卷号1626
期号1
DOI10.1088/1742-6596/1626/1/012051
英文摘要Due to its own advantages, MMC-HVDC transmission system has been widely used in power transmission and grid connection. According to the existing double-terminal traveling wave fault location method of MMC-HVDC transmission lines, a double-terminal traveling wave location method is proposed, which is not affected by wave velocity. The wavelet transform is performed on the voltage traveling wave signals at both ends to determine the time when the traveling wave reaches both ends of the line, and the distance of the fault point is calculated. It effectively reduces the influence of the uncertainty of traveling wave velocity on the positioning results and improves the positioning accuracy. The simulation of PSCAD and Matlab software proves the effectiveness and correctness of the method. © Published under licence by IOP Publishing Ltd.
会议录Journal of Physics: Conference Series
会议录出版者IOP Publishing Ltd
语种英语
ISSN号17426588
内容类型会议论文
源URL[http://ir.lut.edu.cn/handle/2XXMBERH/132616]  
专题电气工程与信息工程学院
作者单位1.National Demonstration Center for Experimental Electrical and Control Engineering Education, Lanzhou University of Technology, Gansu, China
2.College of Electrical and Information Engineering, Lanzhou University of Technology, Gansu, China;
3.Key Laboratory of Gansu Advanced Control for Industrial Processes, Lanzhou University of Technology, Gansu, China;
推荐引用方式
GB/T 7714
Zhang, Mingguang,Yang, Chengming,Liu, Zilin,et al. Research on the Fault Location Method of Double-terminal MMC-HVDC Transmission Line without the Influence of Wave Velocity[C]. 见:. Beijing, China. June 21, 2020 - June 22, 2020.