CORC  > 广州能源研究所  > 中国科学院广州能源研究所
Conventional and advanced exergy analyses of an air-conditioning system in a subway station
Yin, Hua2,3; Guo, Huafang2,3; Tang, Zhihua2,3; Yu, Junyan1; Lu, Haiyang4
刊名INTERNATIONAL JOURNAL OF EXERGY
2019
卷号29期号:2-4页码:236-262
关键词conventional and advanced exergy analyses air-conditioning system subway station
ISSN号1742-8297
通讯作者Guo, Huafang(guohf@ms.giec.ac.cn)
英文摘要Air-conditioning systems in subway stations consume a large amount of energy. In this study, conventional and advanced exergy analyses were carried out to determine the energy-saving potential of an air-conditioning system in a subway station. Results show that air handling unit (AHU) should be improved for the highest values of relative irreversibility (RI) with conventional exergy analysis, whereas the compressor should have the highest improvement priority for the largest avoidable exergy destruction with advanced exergy analysis. Moreover, influences of compressor efficiency, condensation temperature, and evaporation temperature on avoidable exergy destruction of the air-conditioning system were also investigated. According to the findings, compressor efficiency significantly influences the system's total avoidable exergy destruction. The lower the compressor efficiency, the more rapidly the avoidable exergy destruction of the compressor increases. Furthermore, the avoidable exergy destruction of condenser, compressor, cooling tower (CT), and cooling water pump (CWP) increases with the rise of the condensation temperature, whereas that of the evaporator, throttling valve (TV), condenser, compressor, CT, and CWP decreases with the rise of the evaporation temperature.
资助项目Guangdong Science and Technology Program[2017A020216006] ; Guangdong Science and Technology Department
WOS关键词CARBON-DIOXIDE ; ENERGY ; DESTRUCTIONS ; OPTIMIZATION ; PLANT ; CYCLE ; HVAC
WOS研究方向Thermodynamics ; Energy & Fuels
语种英语
出版者INDERSCIENCE ENTERPRISES LTD
WOS记录号WOS:000473551500007
资助机构Guangdong Science and Technology Program ; Guangdong Science and Technology Department
内容类型期刊论文
源URL[http://ir.giec.ac.cn/handle/344007/25306]  
专题中国科学院广州能源研究所
通讯作者Guo, Huafang
作者单位1.Guangzhou Metro Grp Co Ltd, Tower A,Wansheng Sq,1238 Xingang East Rd, Guangzhou 510330, Guangdong, Peoples R China
2.Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China
3.Guangdong Key Lab New & Renewable Energy Res & De, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China
4.Guangdong Univ Technol, Sch Automated Inst, Waihuan West Rd, Guangzhou 5100006, Guangdong, Peoples R China
推荐引用方式
GB/T 7714
Yin, Hua,Guo, Huafang,Tang, Zhihua,et al. Conventional and advanced exergy analyses of an air-conditioning system in a subway station[J]. INTERNATIONAL JOURNAL OF EXERGY,2019,29(2-4):236-262.
APA Yin, Hua,Guo, Huafang,Tang, Zhihua,Yu, Junyan,&Lu, Haiyang.(2019).Conventional and advanced exergy analyses of an air-conditioning system in a subway station.INTERNATIONAL JOURNAL OF EXERGY,29(2-4),236-262.
MLA Yin, Hua,et al."Conventional and advanced exergy analyses of an air-conditioning system in a subway station".INTERNATIONAL JOURNAL OF EXERGY 29.2-4(2019):236-262.
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace