Study on Hydrogen Fluoride at High Temperature Detection Method with Temperature Correction Based on Laser Technology
He Ying1,2; Zhang Yu-jun1; You Kun1; Gao Yan-wei1; Chen Chen1; Liu Wen-qing1
刊名SPECTROSCOPY AND SPECTRAL ANALYSIS
2017-03-01
卷号37期号:3页码:964-970
关键词Laser Absorption Spectroscopy Temperature Correction Concentration Inversion Algorithm Multiple Reflection Cell Hydrogen Fluoride
DOI10.3964/j.issn.1000-0593(2017)03-0964-07
文献子类Article
英文摘要Hydrogen fluoride(HF) is one of the important character gases for fault diagnosis of gas insulation switch (GIS) in the system of substation equipment. The high-accuracy, fast- response and real-time detection method of HF is a focus in industrial and environmental fields. In this research, the HF detection experiment system was set up at first based on laser absorption spectroscopy technology combined with anti-corrosion multiple reflection cell made by monel steel. Moreover, the laser absorption spectral characteristics of HF at different temperature were analyzed, then the coefficient partition function curve and absorption linestrength curve according to the distribution function coefficient in HITRAN database were studied. As the most important work, the concentration inversion algorithm was designed here with HF character spectrum analysis and temperature parameter correction method for accurate concentration inversion after the basic study. At last, the continuous experimental results were obtained by HF sample gases of different concentration considerating the temperature characteristic of the multiple reflection cell. When the multiple reflection cell was heat and stay stably, the biggest detection error of concentration inversion was 5. 33% and 5. 87% at 313 and 323 K respectively without temperature correction, and that was 1.20% and 1. 47% respectively after temperature correction. By continuous detection and culculation, the detection limit is 8.7 X 10(-5) mmol . mor(-1) at 323 K which is a little higher than 6.3 X 10(-5) mmol . mol(-1) at 290 K(20 m optical length). Although the detection error with temperature correction at high temperature was higher than it at room temperature, the results show that it was lower than that without correction at the same temperature. It was verified that the this spectrum detection method and concentration inversion algorithm works stably and reliably, so this technology could realize HF real-time monitoring demand in chemical production field and it will provide the effective technical support in gas emission regulation in safety and environment protection for our country.
WOS研究方向Spectroscopy
语种英语
WOS记录号WOS:000397352600053
资助机构National Key Scientific Instrument and Equipment Development Projects(2012YQ22011902) ; National Key Scientific Instrument and Equipment Development Projects(2012YQ22011902) ; National Key Scientific Instrument and Equipment Development Projects(2012YQ22011902) ; National Key Scientific Instrument and Equipment Development Projects(2012YQ22011902) ; 863 National High Technology Research and Development Program of China(2014AA06A503) ; 863 National High Technology Research and Development Program of China(2014AA06A503) ; 863 National High Technology Research and Development Program of China(2014AA06A503) ; 863 National High Technology Research and Development Program of China(2014AA06A503) ; National Key Scientific Instrument and Equipment Development Projects(2012YQ22011902) ; National Key Scientific Instrument and Equipment Development Projects(2012YQ22011902) ; National Key Scientific Instrument and Equipment Development Projects(2012YQ22011902) ; National Key Scientific Instrument and Equipment Development Projects(2012YQ22011902) ; 863 National High Technology Research and Development Program of China(2014AA06A503) ; 863 National High Technology Research and Development Program of China(2014AA06A503) ; 863 National High Technology Research and Development Program of China(2014AA06A503) ; 863 National High Technology Research and Development Program of China(2014AA06A503)
内容类型期刊论文
源URL[http://ir.hfcas.ac.cn:8080/handle/334002/31756]  
专题合肥物质科学研究院_中科院安徽光学精密机械研究所
作者单位1.Chinese Acad Sci, Key Lab Environm Opt & Technol, Anhui Inst Opt & Fine Mech, Hefei 230031, Peoples R China
2.Univ Sci & Technol China, Hefei 230026, Peoples R China
推荐引用方式
GB/T 7714
He Ying,Zhang Yu-jun,You Kun,et al. Study on Hydrogen Fluoride at High Temperature Detection Method with Temperature Correction Based on Laser Technology[J]. SPECTROSCOPY AND SPECTRAL ANALYSIS,2017,37(3):964-970.
APA He Ying,Zhang Yu-jun,You Kun,Gao Yan-wei,Chen Chen,&Liu Wen-qing.(2017).Study on Hydrogen Fluoride at High Temperature Detection Method with Temperature Correction Based on Laser Technology.SPECTROSCOPY AND SPECTRAL ANALYSIS,37(3),964-970.
MLA He Ying,et al."Study on Hydrogen Fluoride at High Temperature Detection Method with Temperature Correction Based on Laser Technology".SPECTROSCOPY AND SPECTRAL ANALYSIS 37.3(2017):964-970.
个性服务
查看访问统计
相关权益政策
暂无数据
收藏/分享
所有评论 (0)
暂无评论
 

除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。


©版权所有 ©2017 CSpace - Powered by CSpace