Norton equivalent circuit for current control loop of grid-connected system | |
Tang C(汤赐) ; Yang G(杨耕) ; Tan JT(谭惊涛) ; TANG Ci ; YANG Geng ; TAN Jing-tao | |
2016-03-30 ; 2016-03-30 | |
关键词 | grid-connected system PWM inverter LCL output filter weak distributed power system TM464 |
其他题名 | Norton equivalent circuit for current control loop of grid-connected system |
中文摘要 | Modeling method for the current control loop of a grid-connected PWM inverter with the LCL output filter was discussed.Firstly,the current control loop with the LCL inverter-side current as feedback was established.Then,parameters of PI controller were calculated on the basis of an equivalent controlled object.Finally,Norton equivalent circuit for the current control loop of grid-connected system was derived by integrating one control equation,which connected the PWM inverter output voltage and the LCL inverter-side current,with two circuit equations,separately using the LCL inverter-side current and the injected current as loop currents.With the induced Norton equivalent circuit,system-level resonant and unstable issues on real grid-connected system applied in weak distributed power systems can be easily analyzed.The validity of substituting Norton equivalent circuit for grid-connected system is verified by simulation and experiment.; Modeling method for the current control loop of a grid-connected PWM inverter with the LCL output filter was discussed.Firstly,the current control loop with the LCL inverter-side current as feedback was established.Then,parameters of PI controller were calculated on the basis of an equivalent controlled object.Finally,Norton equivalent circuit for the current control loop of grid-connected system was derived by integrating one control equation,which connected the PWM inverter output voltage and the LCL inverter-side current,with two circuit equations,separately using the LCL inverter-side current and the injected current as loop currents.With the induced Norton equivalent circuit,system-level resonant and unstable issues on real grid-connected system applied in weak distributed power systems can be easily analyzed.The validity of substituting Norton equivalent circuit for grid-connected system is verified by simulation and experiment. |
语种 | 英语 ; 英语 |
内容类型 | 期刊论文 |
源URL | [http://ir.lib.tsinghua.edu.cn/ir/item.do?handle=123456789/147119] |
专题 | 清华大学 |
推荐引用方式 GB/T 7714 | Tang C,Yang G,Tan JT,et al. Norton equivalent circuit for current control loop of grid-connected system[J],2016, 2016. |
APA | 汤赐,杨耕,谭惊涛,TANG Ci,YANG Geng,&TAN Jing-tao.(2016).Norton equivalent circuit for current control loop of grid-connected system.. |
MLA | 汤赐,et al."Norton equivalent circuit for current control loop of grid-connected system".(2016). |
个性服务 |
查看访问统计 |
相关权益政策 |
暂无数据 |
收藏/分享 |
除非特别说明,本系统中所有内容都受版权保护,并保留所有权利。
修改评论